Static Synchronous Compensator, also known as SVG (Static Var Generator)
The dust filter can not be cleaned regularly, the dust and water will be inhaled into power modules, and then, the mud will be attached to power boards.
Cooling air will change direction after they come through basement louvre, then go up to enter the container through dust filter at the bottom of STATCOM. After heat exchange, hot air will be forced to go out from container back. The gravity of sands will sink after changing direction from basement louvre. This solution is very suitable for sands area.
System Parameters | |||
Rated voltage | 3kV~35kV | ||
Input voltage range | 0.2~1.2Pu | ||
Grid frequency | 50±0.5Hz | ||
Rated capacity | ±1Mvar ~ ±120Mvar | ||
Full load power loss | <0.8% | ||
Total harmonic current distortion | ≤3%, meeting GB/T14549-1993 | ||
Total PCC harmonic voltage distortion | ≤3%, meeting GB/T14549-1993 | ||
Response time | <5ms | ||
Overload capacity | 1.1 times over-load, long time operation; 1.2times over-load for 1minute, trip | ||
Fault treatment | Redundancy design meeting automatic N-1 operation | ||
Operation mode | Constant reactive power mode, constant voltage mode, constant power factor mode, load compensation mode, Voltage& Reactive power integrated control mode | ||
Communication protocol | Modbus, IEC104 | ||
Monitoring mode | Local/remote control | ||
HMI | LCD touch screen in English | ||
Signal transmission | Optical-fiber communication | ||
Key technology | Instantaneous reactive power theory, SPWM theory, decoupling control technology, capacitor voltage balance control technology, three-phase independent control technology, single pole multiple frequency technology, carrier phase-shifting SPWM theory, chain link temperature real-time monitoring technology | ||
Power interface | 380VAC, 220VDCdual circuits dual redundancy power supply | ||
Main protection function | Over-current, Over-voltage, drive fault, Power unit over voltage, over-current, over-temperature, communication faults etc. water-cooling failure | ||
Wiring method | Star connection or Delta connection | ||
Cooling method | Air cooling, water cooling | ||
Protection class | Indoor IP30 | Container: IP54 | |
Installation method | Indoor | Outdoor | |
Service life | 30Years | ||
Operation environment | |||
Ambient temperature | -25℃~+45℃ | ||
Storage environment temperature | -40℃~+70℃ | ||
Altitude | 2000m(To be customized in case of > 2000m | ||
Relative humidity | ≤90%, no condensation | ||
Pollution grade | Class IV | ||
Executive standard | DL/T 1215.1-2013,GB/T 14549-1993,GB/T 17626.2-2006,GB/T 17626.3-2006,GB/T 17626.4-2008,GB/T 17626.5-2008,GB/T 17626.11-2008 |